Symphony 3000VA/3000W Online Rack/Tower UPS 2U 230V

SKU: SPY3000RMi2U VA: 3000 Watts: 3000

Looking for a quotation or want to request further information about this product?

Call us today: 0845 561 0560

3kVA true online UPS with a full 3000W output

The Symphony SPY3000RMi2U is a 3kVA single-phase, online double-conversion UPS designed by Uniti Power for server racks, network and communications rooms, healthcare systems and other critical 230V equipment. With an output power factor of 1.0 it supplies the full 3000W, switches to battery with no break in supply, and installs in 2U of a 19-inch rack or stands upright as a tower.

The inverter supplies the load continuously, so connected equipment is isolated from power cuts, sags, surges, frequency variation and electrical noise. Output voltage is regulated to within ±1%, and online efficiency of up to 93% keeps running costs and heat output down in busy server and comms spaces.

Where the SPY3000RMi2U is used

Typical applications include server rooms and data networks, enterprise and edge computing, telecoms and networking equipment, healthcare and laboratory systems, and industrial control.

Power quality and efficiency

  • 0ms transfer to battery: the output carries on without interruption when the mains fails.
  • Regulated output: ±1% voltage accuracy, under 1% THDv on linear loads and a 3:1 crest factor.
  • Wide input window: 160-300V at full load, and down to 110V with derating, so normal voltage dips are handled without using the batteries.
  • Low input distortion: input power factor above 0.99 and THDi below 5%.
  • Efficiency: up to 93% in online mode and up to 97% in ECO mode, with a 10ms transfer back to the inverter from ECO.
  • Frequency converter mode: 50Hz / 60Hz conversion (CVCF) at up to 60% load.

Runtime and battery expansion

Six internal 12V 9Ah batteries (72V DC) give a typical 3.5 minutes at the full 3000W load and 9.1 minutes at 1500W. Up to four EBM7218RT2U external battery modules can be connected for longer outages, each one a matching 2U rack/tower unit.

Battery configuration1500W (50% load)3000W (full load)
Internal batteries9.1 min3.5 min
+ 1 x EBM7218RT2U38.8 min16.0 min
+ 2 x EBM7218RT2U75.9 min31.4 min
+ 3 x EBM7218RT2U114.7 min48.4 min
+ 4 x EBM7218RT2U155.0 min67.4 min

The 1.5A charger brings the internal batteries back to 90% in around 3 hours. Use the Run Time tab to estimate runtime at your own load.

Runtimes are typical values for new, fully charged batteries at 25°C, provided as a guide only. Actual runtime depends on battery age, temperature and the type of load.

Outlets and installation

The SPY3000RMi2U has an IEC C20 input and nine outlets: a main group of 1 x IEC C19 and 4 x IEC C13, plus a programmable group of 4 x IEC C13. The programmable group can be switched off during an outage, so non-essential equipment is shed and the most important loads run for longer.

The unit measures 438 x 605 x 86.5mm (2U). Rack ears and tower feet are included, the optional SPYRAIL1-3 rail kit supports it in a 19-inch cabinet, and the dot-matrix LCD rotates for rack or tower use.

Monitoring, communications and safe shutdown

Standard interfaces are USB (HID), RS232, a programmable dry input and output, and an emergency power off (EPO) input. The intelligent slot takes an optional network management card, Modbus card or AS400 dry-contact card, and an optional WLAN module is available. WinPower G2 monitoring software gives live status, alarms and controlled shutdown of connected servers.

Standards, warranty and support

The SPY3000RMi2U is CE marked and built to IEC/EN 62040, the international standard for UPS systems. It meets Category C2 for conducted and radiated emissions, with immunity tested to IEC/EN 61000-4-2, -4-3, -4-4 and -4-5.

Registered Symphony products in the UK carry a 6-year warranty on the UPS electronics and 2 years on batteries and accessories, from the original date of purchase. Installation and commissioning is recommended but is not a condition of the warranty. See warranty information for full terms, and register your UPS once it is installed.

What's in the box

SPY3000RMi2U UPS, 1 x 10A output cable, USB cable, rack ears, tower feet and user manual. An input power cable is not included. An RS232 cable and the SPYRAIL1-3 rail kit are available separately.

Symphony SPY3000RMi2U questions answered

Is the Symphony SPY3000RMi2U a true online UPS?
Yes. The SPY3000RMi2U is an online double-conversion UPS, so the inverter powers the load at all times and the transfer to battery is 0ms.

How much load can the SPY3000RMi2U support?
Up to 3000W. Its output power factor is 1.0, so the VA and watt ratings are equal. In line mode it carries 105-125% overload for 3 minutes and 125-150% for 30 seconds.

How long will the SPY3000RMi2U run on battery?
About 3.5 minutes at full load and 9.1 minutes at half load on its internal batteries, extending to 67.4 minutes at full load and 155.0 minutes at half load with four EBM7218RT2U modules.

What input connection does the SPY3000RMi2U use?
An IEC C20 inlet. The input power cable is not supplied in the box.

Can SPY3000RMi2U units run in parallel?
No, this model does not support parallel operation. For parallel capacity or redundancy, the Symphony 6kVA and 10kVA models accept the SPYPK parallel card.

How do I buy the SPY3000RMi2U?
Request a quote on this page, call 0845 561 0560, or find a Uniti Power partner near you.

Runtime figures are taken from the Symphony Range Brochure (V1.2025, PDF). Full specifications are in the SPY3000RMi2U datasheet (PDF).

  • 3000VA / 3000W unity power factor
  • 93% online efficiency
  • 0ms inverter transfer during normal online operation
  • 2U rack/tower design
  • Extended runtime support
  • IoT and network-management connectivity
Product codeSPY3000RMi2U
Form factor2U rack/tower convertible
Power rating - capacity3000VA / 3000W
Efficiency - double conversion mode93%
Efficiency - ECO mode97%
Input - voltage range160-300V at 100% load; 110-160V derating linearly to 50% load
Input - rated frequency50Hz / 60Hz
Input - frequency range40-70Hz (45-55Hz / 54-66Hz at load >60%)
Input - power factor>0.99
Input - THDi<5%
Input - connectionIEC C20
Output - rated voltage200 / 208 / 220 / 230 / 240VAC (derating 10% at 208V; 20% at 200V)
Output - rated frequency50Hz / 60Hz
Output - maximum power factor1.0
Output - voltage accuracy±1%
Output - THDv<1% linear load; <5% non-linear load
Output - crest factor3:1 maximum
Output - overload (line mode)100-105%: continuous; 105-125%: 3 minutes; 125-150%: 30 seconds; >150%: 500ms
Output - sockets1 x IEC C19 + 8 x IEC C13 (1 main outlet group of 1 x IEC C19 + 4 x IEC C13; 1 programmable outlet group of 4 x IEC C13)
Output - load segment controlYes
Transfer time - line / battery0ms
Transfer time - line / bypass4ms
Transfer time - ECO / inverter10ms
Battery - DC voltage72VDC
Battery - internal battery6 x 12V / 9Ah
Battery - typical backup time9.1 minutes at 50% load; 3.5 minutes at 100% load (internal battery, PF 1.0)
Battery - maximum EBMs4
Battery - compatible EBMEBM7218RT2U (72V, 2U rack/tower)
Runtime (minutes at 1500W / 3000W) - internal battery9.1 / 3.5
Runtime (minutes at 1500W / 3000W) - with 1 EBM38.8 / 16.0
Runtime (minutes at 1500W / 3000W) - with 2 EBMs75.9 / 31.4
Runtime (minutes at 1500W / 3000W) - with 3 EBMs114.7 / 48.4
Runtime (minutes at 1500W / 3000W) - with 4 EBMs155.0 / 67.4
Charger - charging current1.5A
Charger - recharge time3 hours to 90%
Operating modes - CVCF (frequency converter)Yes (derating to 60% load)
Operating modes - parallel operationNo
DisplayDot matrix LCD, manually rotatable (optional segment LCD)
Display & communications - languages10
Display & communications - USBUSB 2.0 with HID
Display & communications - RS232Yes, DB9
Display & communications - dry I/O1 programmable dry input; 1 programmable dry output
Display & communications - EPOYes
Display & communications - intelligent slotYes, long card
Display & communications - network cardOptional, NMC long card
Display & communications - Modbus cardOptional, CMC/Modbus long card
Display & communications - dry contact cardOptional, AS400 long card
Display & communications - WLAN moduleOptional, HDMI type
Display & communications - IoT EthernetRJ45
Display & communications - monitoring softwareWinPower G2
Physical - dimensions (W x D x H)438 x 605 x 86.5mm (2U)
Physical - IP ratingIP20
Environment - operating temperature0-40°C
Environment - nominal battery temperature20-25°C
Environment - relative humidity0-95%
Environment - operating altitude0-3000m (load derates 1% per 100m from 1000-3000m)
Environment - acoustic noise<50dB at typical load, battery fully charged
Standards & certification - certificationCE, IEC/EN 62040
Standards & certification - EMI (conducted / radiated)Category C2
Standards & certification - ESDIEC/EN 61000-4-2
Standards & certification - radiated immunityIEC/EN 61000-4-3
Standards & certification - EFTIEC/EN 61000-4-4
Standards & certification - surgeIEC/EN 61000-4-5
In the box & accessories - input power cableNo
In the box & accessories - output power cableYes, 1 x 10A
In the box & accessories - EBM cableYes (supplied with EBM)
In the box & accessories - USB cableYes
In the box & accessories - RS232 cableOptional
In the box & accessories - rail kitOptional, SPYRAIL1-3
In the box & accessories - tower feetYes
In the box & accessories - rack earsYes
In the box & accessories - manualYes

Symphony SPY3000RMi2U battery runtime

How long the SPY3000RMi2U runs on its internal batteries and with up to four EBM7218RT2U external battery modules.

Runtime by load and battery configuration
Configuration750 W (25%)1.5 kW (50%)2.25 kW (75%)3 kW (100%)
Internal batteries20.5 min9.1 min5.5 min3.5 min
+ 1 x EBM7218RT2U1 h 24 min38.8 min23.2 min16.0 min
+ 2 x EBM7218RT2U2 h 44 min1 h 16 min45.5 min31.4 min
+ 3 x EBM7218RT2U4 h 08 min1 h 55 min1 h 10 min48.4 min
+ 4 x EBM7218RT2U5 h 36 min2 h 35 min1 h 36 min1 h 07 min
  • 1.5 kW (50%) and 3 kW (100%) load figures are published in the Symphony Range Brochure (V1.2025). Other loads are estimated from the battery discharge characteristics and calibrated to those figures.
  • Disclaimer: all runtimes are typical values, provided as a guide only and not guaranteed. They assume new, fully charged batteries at 25°C and a load with a power factor of 1.0. Actual runtime depends on battery age and condition, ambient temperature, the type of load and how recently the batteries were charged, and will be shorter as batteries age. Estimates over 2 hours should be treated with particular caution.
  • For a runtime calculation for your site, contact Uniti Power.